LogicPLUS-S Two-Wire Controller
5
Wire type: Single strand direct burial, Jacketed two conduc-
tor, or Stranded. No “Special” wire required.
Wire Size: Minimum 14 gauge.
Wire Runs: Maximum 12,000 feet for each two wire path
(4 available).
Branching & Teeing:
Allowed but should be well planned and
minimized.
Wire Color: Use of different colored wires is recommended
for ease of wire run identication. Use different
colors for each run and every tee or branch.
Wiring Installation:
Each individual output, including branches or
tees, should be kept separate from the wiring of
other outputs.
the wires of a eld output with
those of another OR any branch or tee.
the eld wires back to the
controller OR back onto themselves.
wire
connections/splices. All wire connections/splices
should be made in valve boxes.
A maximum of 8 valves, any where on the system, may operate simultaneously, of either the
same number or combinations of different numbers. The 8 valve maximum plus 3 master
valves (A, B, C) plus 1 fertigation valve.
One of the most critical installation requirements of a LogicPLUS-S two wire system is the
quality of your wire connections. If you follow these directions you will have a reliable, depend-
able control system for many years. It is suggested to soldier all receiver (red wire) connec-
tions to your main two-wire run. Next install the soldiered two-wire connection in a waterproof
underground connector housing. When soldering is impractical, a waterproof “dry-type” Hit
Products DBC-BR wire connector is required. The above mentioned product will provide an
uncontaminated, dry connection. A pair of DBC-BR connectors are included with every LP-RP
Receivers for the connection of each Receiver to the two wire path.
.